Immersion Cooling:
Facility Infrastructure
Design Guide
Choosing immersion cooling is the easy part. The engineering challenge is everything around the tank — CDU sizing, dielectric fluid management, secondary water loop design, structural loading, fire suppression, electrical modifications, and the transition strategy from air-cooled infrastructure. This is that guide.
The data centre industry has reached a thermal inflection point. Air cooling — the default since the first raised-floor computer rooms of the 1960s — is structurally incapable of serving the rack densities that AI and HPC workloads demand. A rack of NVIDIA H100 GPUs draws 10–14 kW per server; a fully populated 42U rack exceeds 60–80 kW. Air, with its poor volumetric heat capacity, cannot remove that heat without airflow velocities that create acoustic, structural, and operational problems.
Immersion cooling removes heat directly from the chip surface through a liquid medium with heat capacity 1,200× greater than air. But immersion cooling is not simply a matter of replacing the CRAC units. It rewrites the infrastructure design of a data centre from the floor slab upward. This article is the engineering reference for facility designers, MEP consultants, and data centre operators moving from technology selection into facility design.
Technology Types: What the Facility Sees
There are three commercially deployed immersion cooling technologies. The technology choice must be locked before facility design begins — each imposes fundamentally different infrastructure requirements that are not interchangeable at fit-out stage.
Single-Phase Liquid Immersion (SLI)
Servers submerged in dielectric fluid (mineral oil, synthetic ester, or engineered fluid). Fluid remains liquid — heat removed via a CDU pumping fluid through a heat exchanger. Most mature technology; retrofittable; fluid management straightforward. GRC, Submer, LiquidStack are leading vendors.
Two-Phase Liquid Immersion (2PLI)
Servers submerged in low-boiling-point fluorocarbon fluid. Fluid boils at the chip surface; vapour rises and condenses on water-cooled coils above the tank, then drips back. High heat flux capacity; near-zero pump energy. More complex fluid handling; GWP concerns on some fluorocarbons.
Direct Liquid Cooling (DLC) — Hybrid
Cold plates attached directly to CPUs/GPUs; coolant circulates through the plate. Remainder of server is air-cooled. Widely adopted by hyperscalers as a transitional path. Lower facility disruption than full immersion; less effective for very high-density GPU configurations above 60 kW/rack.
Rear-Door Heat Exchanger (RDHx)
Heat exchanger on the rear door of a standard rack cools exhaust air before it re-enters the room. Not full immersion but bridges the density gap — works with existing servers at densities up to ~30 kW/rack without supplementing room cooling. A common first step before full liquid immersion.
Technology selection drives facility design: Single-phase requires a secondary water loop, CDU room, and fluid top-up infrastructure. Two-phase requires a vapour management system and fluorocarbon handling procedures. DLC requires a facility-wide chilled water loop to every rack. Commit to a technology before issuing MEP design briefs — these are not interchangeable at construction stage.
The CDU and Secondary Water Loop
In single-phase immersion, the Coolant Distribution Unit (CDU) sits between the dielectric fluid loop (primary, in contact with servers) and the facility water loop (secondary, connecting to chillers or cooling towers). Designing this interface correctly determines system efficiency, redundancy, and maintainability for the facility’s lifetime.
CDU Thermal Sizing
// CDU Thermal Capacity Sizing Q_CDU = N_tanks × P_rack × LF × SF Where: N_tanks = Number of immersion tanks served P_rack = Max IT power per tank (kW) LF = Load factor (0.85–0.95 for AI) SF = Safety factor (1.15–1.25) // Example: 10-tank deployment, 100 kW/tank, LF=0.90, SF=1.20 Q_CDU = 10 × 100 × 0.90 × 1.20 = 1,080 kW // Secondary-side flow rate (ΔT = 10°C, water) V_sec = Q_CDU / ( ρ × Cp × ΔT ) = 1,080 / ( 1000 × 4.18 × 10 ) = 25.8 L/s → ~93 m³/hr
-
01
Supply Temperature — The Free Cooling Opportunity
Unlike air-cooled servers requiring 7–12°C chilled water, single-phase immersion tanks typically accept secondary water supply at 25–45°C. This opens free cooling for 6,000–8,000 hours/year in most Indian climates — dramatically reducing chiller run hours and delivering the biggest PUE gain from immersion cooling beyond eliminating CRAC units entirely.
-
02
Variable Flow — Mandatory
AI server loads vary significantly with job scheduling — 100% during training, less than 30% during inference idle. Fixed secondary flow wastes pump energy and causes low-delta-T syndrome, forcing oversized chiller capacity. VFDs on all secondary loop pumps are mandatory, controlled by differential pressure setpoint across the CDU manifold.
-
03
N+1 Redundancy with Hot-Swap Isolation
CDUs must be N+1 for Tier III. Pump sets N+1 with auto-changeover. Fluid loop isolation valves at each CDU inlet and outlet allow hot-swap maintenance without draining immersion tanks — operationally non-negotiable. Include sample and drain valves at low points for fluid quality testing without full system shutdown.
Dielectric Fluid Selection and Management
Fluid selection affects material compatibility, fire risk classification, environmental liability, supply chain logistics, and spill cost. The three primary single-phase fluid categories each make different trade-offs that must be evaluated against the specific facility context.
| Fluid Type | Flash Point | K-Factor (cSt @ 40°C) | Material Compatibility | Environmental | Cost (approx. per litre) |
|---|---|---|---|---|---|
| White Mineral Oil | 135–155°C | 8–12 | Degrades EPDM seals; attacks some plastics | Petroleum-based; spill risk | ₹80–120 |
| Synthetic Ester | >260°C | 28–35 | Compatible with most seals and metals | Readily biodegradable (>90% in 28 days) | ₹280–420 |
| Engineered Dielectric | >300°C | 15–22 | Formulated for server hardware; plastics safe | Low toxicity; biodegradable formulations | ₹600–1,200 |
| Fluorocarbon (2-phase) | Non-flammable | <1 | Excellent — inert to all materials | GWP 297–9,300; EU F-Gas restricted | ₹3,500–12,000 |
Fluorocarbon supply risk: 3M announced the discontinuation of Novec fluid production by end-2025. Any two-phase system designed around 3M Novec fluids must plan for alternative sourcing (Solvay, AGC) or evaluate transition to next-generation low-GWP fluids. This is a material procurement risk for new projects — raise it explicitly with clients at concept stage before specifying two-phase technology.
Every immersion installation requires dedicated fluid management infrastructure that is frequently omitted from concept designs: a fluid storage tank sized at 110% of the largest single tank volume; a fill/drain station with pump, hose reel, and drip trays at each tank row; bunded floor containment with a blind sump not connected to site sewer; and fluid quality monitoring ports for dielectric strength, viscosity, and particle count sampling at CDU inlet and outlet.
Structural and Civil Requirements
This is where immersion cooling most frequently catches facility designers by surprise. A filled immersion tank is extraordinarily heavy — and most existing data centre floor slabs are not designed for it.
Floor Loading: 1,500–2,500 kg/m²
A GRC ICEtank holds ~1,200 litres of fluid plus servers on a 0.6 m² footprint — equivalent UDL of 2,300–3,300 kg/m². Standard raised-floor data halls are rated 1,200 kg/m² UDL. Immersion tanks require ground floor, reinforced slabs, or structural assessment and strengthening before installation.
Raised Floor Incompatibility
Standard 600×600 mm raised floor panels rated 12 kN concentrated load are insufficient. Ground-floor or solid concrete slab deployment is standard. Where a raised floor exists, tanks must sit on stringer-supported platforms engineered to transfer load to column bases — structural engineer is mandatory on the design team.
Maintenance Clearance
Server extraction from open-top tanks requires 1.5–2.0 m clear height above the tank lid. Hoist or monorail recommended for tanks deeper than 1.2 m. Minimum 1.5 m aisle width on each side of the tank row — wider than standard hot/cold aisle designs — for fluid handling and server swap operations.
Drainage and Spill Containment
Floor drains must not route dielectric fluid to sewer — it requires specialist disposal. Bunded zones with blind sumps and pump-out are required. Tank overfill protection via high-level float switch and automatic pump-off is mandatory. Containment volume per BS EN 1825 or local fire authority requirements.
Electrical Infrastructure Modifications
Immersion cooling changes the electrical design of a data centre in several significant ways beyond simply removing CRAC unit power circuits.
Busway Sizing for High-Density Rows
An immersion-cooled row supporting 10 tanks at 100 kW each draws 1,000 kW per row. Standard data centre bus ducts rated for 100–250A tap-offs are undersized for this density. Row-level busway must be resized — typically 630A or 800A busbars with 250A or 400A tap-offs per tank. Voltage drop along the busbar run must be calculated; immersion tank OEMs specify maximum supply impedance to maintain server input voltage within ±5%.
CDU Power on UPS-Backed Supply
CDUs require their own power feed — typically 5–15 kW per CDU for pump motors, controls, and instrumentation. This load must appear on the electrical load schedule as a separate mechanical service load (not IT load) to avoid distorting PUE calculations. CDU feeds must be on the UPS-backed critical bus — a CDU losing power during high IT load causes rapid dielectric fluid temperature rise leading to thermal throttling or server shutdown within minutes.
Earthing and Bonding
All metallic tank bodies must be bonded to the facility equipotential earth system. The dielectric fluid is non-conductive but servers within the tank remain live — the tank body provides the grounding path for server chassis earth conductors. Static charge accumulation in flowing dielectric fluid also requires earth continuity verification across all pipe flanges and tank connections. See KVRM’s earthing and grounding design guide → for the full methodology.
Fire Suppression and Detection
Fire protection for immersion-cooled rooms requires a complete rethink from standard data centre practice. The risk profile is fundamentally different — and in some respects significantly better than air-cooled rooms.
Immersion cooling dramatically reduces the ignition risk of servers — no hot spots, no fan motors, no cable trays carrying hot exhaust air. But if ignition occurs within the fluid, the suppression agent must be compatible with the dielectric fluid and the hold time must be sufficient for fluid to cool below its flash point.
| Suppression Agent | Compatibility with Mineral Oil | Compatibility with Synthetic Ester | Recommendation for Immersion Rooms |
|---|---|---|---|
| Water Mist (Fine) | Compatible | Compatible | Preferred. Suppresses fire above tank without fluid contamination. Avoids the flooding cost of clean agent systems. |
| FM-200 / HFC-227ea | Compatible | Compatible | Effective. Hold time minimum 10 minutes — fluid re-ignition risk if agent dissipates before fluid cools below flash point. |
| Novec 1230 / FK-5-1-12 | Compatible | Compatible | Lower GWP than FM-200. Verify supply continuity with contractor — 3M Novec product family production is winding down. |
| CO₂ Total Flooding | Compatible | Compatible | Effective but requires full room evacuation before discharge. Not suitable for frequently accessed immersion rooms. |
| AFFF / Foam | Contaminates fluid | Contaminates fluid | Do NOT specify. Foam contamination requires complete fluid replacement — ₹15–50 lakh per tank in synthetic ester cost alone. |
Detection: Standard point-type smoke detectors are largely ineffective in immersion rooms — closed tanks suppress smoke release from incipient faults. Specify VESDA aspirating systems with sampling points at tank lids and CDU enclosures. Supplement with VOC gas detection for synthetic ester overheating events. See KVRM’s clean agent fire suppression guide → for agent selection methodology.
PUE, WUE and Heat Recovery
PUE 1.03–1.10 Achievable
Eliminating CRAC units removes 0.10–0.20 from PUE directly. CDU pump energy adds back 0.01–0.02. Warm fluid operation enabling free cooling reduces chiller contribution to near zero for large fractions of the Indian year. The remaining PUE overhead is transformer losses, UPS losses, and lighting.
WUE <0.2 L/kWh Possible
Air-cooled data centres using cooling towers: WUE 1.0–2.5 L/kWh. Immersion with dry coolers: WUE near zero. Use dry cooler or adiabatic cooler on the secondary loop to minimise water consumption — increasingly important for Indian facilities in water-stressed locations.
Waste Heat Recovery at 40–50°C
Secondary loop return temperature of 40–50°C is usable for building heating, absorption cooling, or ORC power generation. Not widely implemented in India yet but increasingly specified by hyperscalers with net-zero commitments. Design the secondary loop piping to accommodate a future heat recovery connection without system modification.
GPU Performance Uplift
Sustained GPU clock speeds run 5–15% higher in immersion than in air-cooled equivalents — GPUs thermal throttle less in isothermal fluid. This is a measurable compute-per-watt improvement that reduces effective power cost per AI training job and is now factored into hyperscaler TCO models for cooling technology selection.
Transition Strategy: Air to Immersion
Few data centres will be purpose-built for immersion from day one. The transition strategy requires careful MEP planning to avoid service interruption and stranded asset costs.
- 01
Phase 1 — Purpose-Built Immersion Wing
Designate a new data hall extension or a dedicated bay as the immersion zone. Ground slab, secondary water loop, CDU room, and modified suppression system installed to serve only that zone. Existing air-cooled halls untouched. The most common and lowest-risk entry path used by Indian colocation operators today.
- 02
Phase 2 — DLC Overlay on Existing High-Density Racks
Direct liquid cooling cold plates fitted to GPUs in existing racks while remaining server components continue air cooling. Facility water loop extended to rack level via manifolds. This requires the existing chilled water system to serve rack-level supply at 18–22°C — most existing 7/12°C plants are compatible with valve adjustment.
- 03
Phase 3 — Progressive Immersion Conversion
As servers reach end-of-life, replace air-cooled racks with immersion tanks bay by bay. Structural assessment and slab reinforcement on a bay-by-bay basis. CRAC units on converted bays decommissioned but retained on adjacent bays until full conversion. Phased approach spreads capital cost over 3–5 years.
- 04
Phase 4 — Unified Warm Water Loop
Once the majority of capacity is immersion-cooled, a unified secondary water loop (35–45°C) replaces the original chilled water plant serving air-cooled zones. Remaining chilled water capacity retained only for ancillary spaces. Net chiller plant typically reduced by 60–75% of original installed capacity at full conversion.
India-Specific Design Considerations
Designing immersion cooling infrastructure for Indian data centre locations introduces constraints and opportunities not present in European or North American designs.
Ambient Temperature and Free Cooling Hours
Mumbai, Chennai, and Hyderabad ambient temperatures exceed 35°C for 2,000–3,000 hours per year — limiting free cooling on warm fluid loops. Adiabatic pre-cooling of dry cooler inlet air extends free cooling hours economically. Delhi and Pune have more favourable winter profiles. Design the control system to maximise free cooling hours with automated switchover between free cooling and mechanical cooling modes based on ambient wet-bulb temperature.
Secondary Loop Water Quality
Indian municipal water supply carries high TDS in many locations. Secondary water loop requires chemical treatment and softening to prevent scale deposition on CDU heat exchanger plates. Scale buildup of even 0.5 mm increases thermal resistance by 20–40% — a common cause of CDU under-performance discovered only at full load. Specify a closed-loop glycol treatment system with continuous conductivity monitoring.
Fluid Supply Chain and Lead Times
Synthetic ester and engineered dielectric fluids are currently imported into India — no large-scale domestic production exists. For a 1 MW deployment requiring ~40,000 litres of synthetic ester, import lead times of 8–12 weeks must be factored into construction schedules. Maintain a minimum 20% buffer stock volume on site for top-up. Engage with fluid suppliers at design stage to confirm supply availability and local distribution arrangements before committing to a specific fluid type.
Engineering Specification Checklist
Before issuing the MEP design brief for an immersion-cooled data centre, confirm these parameters are resolved:
| # | Parameter | Guidance | Discipline |
|---|---|---|---|
| 01 | Immersion Technology Type | SLI / 2PLI / DLC — locked before MEP brief issued | Client / IT |
| 02 | IT Load per Tank (kW) | OEM confirmed; safety factor 1.20 applied to CDU sizing | Electrical |
| 03 | Dielectric Fluid Selection | Material compatibility matrix checked vs. all pipe, seal, and pump materials | Mechanical |
| 04 | Secondary Supply Temperature | OEM max inlet temp confirmed; free cooling feasibility assessed for site climate | Mechanical |
| 05 | Floor Loading Assessment | Structural engineer engaged; slab capacity confirmed or strengthening specified | Structural |
| 06 | CDU Room Location and Size | Accessible for maintenance; pipe routes to tank rows <30 m where possible | Mechanical |
| 07 | Fluid Containment Volume | 110% of largest single tank; blind sump drain; no connection to site sewer | Civil / Mechanical |
| 08 | Secondary Loop Water Treatment | Water quality analysis; glycol concentration; scale inhibitor dosing programme | Mechanical |
| 09 | Busway and Tap-Off Rating | 630A or 800A busbar for high-density rows; voltage drop calculation verified | Electrical |
| 10 | CDU on UPS-Backed Supply | CDU pump and controls on critical power bus — not general services bus | Electrical |
| 11 | Fire Suppression Agent | No AFFF or foam. Water mist or clean agent; agent compatibility with fluid confirmed | Fire Protection |
| 12 | Fire Detection Type | VESDA aspirating system; sampling at tank lids and CDU enclosures | Fire Protection |
| 13 | Tank Earthing and Bonding | All tanks bonded to facility MEB; pipe flange earth continuity verified | Electrical |
| 14 | Maintenance Access Clearance | 1.5 m minimum aisle width; hoist provision for tanks deeper than 1.2 m | Civil / Layout |
| 15 | Fluid Supply Chain Confirmed | Supplier confirmed; 8–12 week import lead time; 20% buffer stock planned | Procurement |
Conclusion: Infrastructure-First Thinking
Immersion cooling is not a product you install — it is a systems transformation of the facility. The tank itself is perhaps 20% of the engineering challenge. The other 80% is the secondary water loop, the structural engineering, the electrical modifications, the fluid management infrastructure, the fire suppression rethink, and the transition strategy from existing infrastructure.
Facilities that engage MEP consultants at concept stage — before technology selection is locked and before the structural engineer has signed off on a slab that cannot bear the load — complete on schedule with a system that performs as modelled. Facilities that treat immersion as a late-stage product selection discover the infrastructure implications during construction, at maximum cost.
The data centres that will define Indian AI infrastructure in 2027–2030 are being designed today. Immersion cooling is not a future option in that landscape — it is a present requirement for any facility targeting GPU rack densities above 30 kW.
Planning an Immersion-Cooled Data Centre?
KVRM provides complete MEP design for immersion cooling deployments — CDU sizing, secondary loop design, structural assessment coordination, fire suppression, and electrical infrastructure for high-density data halls across India and the Gulf region.
Request a Free Consultation →